41503026 - SIRCOVER UL 3P 260 A | Socomec
range img

41503026

    General information
  • Product Range: SIRCOVER
  • Long Description: MANUAL TRANSFER SWITCH SIRCOVER UL 3P 260 A
  • Short Description: SIRCOVER UL 3P 260 A
    Certificates and declaration
  • Conformity to standard #1: UL1008
  • Conformity to standard #4: E317092 Vol.1 Sec.8
  • Proposition 65 California: WARNING This product can expose you to chemicals including Styrene, which is known to the State of California to cause cancer. For more information go to : www.P65Warnings.ca.gov
    Container Information
  • EAN13: 3596032762360
  • Package Level 1 Gross Weight: 10.63
  • Package Level 1 Length: 0.01
  • Package Level 1 Width: 0.01
    Main
  • Reference: 41503026
    Ordering
  • Country of origin: FR
    Technical characteristics
      Connection terminals
    • Max. connection section / AWG: 600MCM / 2 X 250MCM
    • Min. connection section / AWG: #4/2 X 1/0
      Mechanical characteristics
    • Endurance (number of operating cycles): 6050
      Short-circuit capacity
    • Max fuse rating (A): 600
    • Short circuit rating at 600 VAC (kA): 100
    • Type of fuse: J
  • Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit capacity (ms): 50
  • Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit rating (kA): 14
  • Auxiliary contacts / Electrical characteristics: AC300
  • Number of Poles: 3
  • Operation voltage 2 P - 3/4 P: 240/600
  • Rated operational current / 240 VAC resistive load (A): 260
  • Rated operational current / 240 VAC “Total System” (A): 260
  • Rated operational current / 480 VAC resistive load (A): 260
  • Rated operational current / 480 VAC “Total System” (A): 260
  • Rated operational current / 600 VAC resistive load (A): 260
  • Rated operational current / 600 VAC “Total System” (A): 200
  • UL General use rating (A): 260