48250501
- General information
- Product Range: DIRIS A-40
- Long Description: DIRIS A-40; Power Metering and Monitoring Device; 110-400 VAC 50/60 Hz; 120-300 VDC; Class 0.5 for the global measurement chain; 3 Digital inputs / 2 Digital outputs; RS485 output; Ethernet output; Modbus TCP; Modbus RTU; BACnet IP; FTP; SMTP; SNTP
- Short Description: DIRIS A-40 Ethernet 3I 2O
- Certificates and declaration
- Conformity to standard #4: -
- Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
- Container Information
- EAN13: 3596033009136
- Package Level 1 Gross Weight: 0.0
- Package Level 1 Length: 0.3
- Package Level 1 Width: 0.4
- Main
- Reference: 48250501
- General product characteristics
- Device type: Power Metering and Monitoring Device
- Ordering
- Country of origin: FR
- Standards and regulations
- Immunity to conducted disturbances: IEC 61000-4-6
- Immunity to electrical fast transients/bursts: IEC 61000-4-4
- Immunity to electrostatic fields in the air: IEC 61000-4-2
- Immunity to power frequency magnetic fields: IEC 61000-4-8
- Immunity to radiated electromagnetic fields: IEC 61000-4-3
- Radiated emissions: CISPR11 GROUP 1 - CLASS A
- Surge immunity in common mode: IEC 61000-4-5
- IEC 61557-12: Class 0.5 for the global measurement chain
- Safety standards: IEC/EN 61010-1
UL 61010-2-030
CSA C22.2 No. 61010-2-030 - UL file number: E257746
- UL product category: PICQ/PICQ7/FTRZ/FTRZ7
- Electromagnetic compatibility
- PMD
- Safety
- Safety standard
- Technical characteristics
- Communication Ports: RS485 output; Ethernet output
- Communication Protocols: Modbus TCP; Modbus RTU; BACnet IP; FTP; SMTP; SNTP
- Communication speed: 9600-115200 bauds
- Physical layer: RS485 2-3 half duplex wires - SELV
- USB port interface: 1 Type B micro USB; Upgrade and configuration of the module
- Input voltage: 110-400 VAC 50/60 Hz; 120-300 VDC
- Power supply type: AC / DC
- Relative humidity: 70 °C / 158 °F / 97% RH (IEC 60068-2-30)
- Storage temperature: -25 … +85 °C (IEC 60068-2-1/IEC 60068-2-2)
- Impact resistance: Front panel: 5J - casing: 1J (IEC 61010-1 Ed 3.0)
- Maximum operating altitude: 6560 feet / 2000 m
- Operating temperature: -10 … +70 °C / +14 °F … +158 °F (IEC 60068-2-1/IEC 60068-2-2)
- PEP ecopassport - ISO 14025: SOCO-000007-V01.01-EN
- Vibration: 0.35 mm, 25 Hz, 20 min/axe (IEC 61557-12)
- Datalogging: Yes
- Webserver version: WEBVIEW-S
- Accuracy class: Class 0.5
- Active Power accuracy: Class 0.2 ANSI C12.20
Class 0.5 for the global measurement chain according to IEC 61557-12 from 2% up to 120% of the rated current (with TE/TF sensors) - Current measurement type: AC
- External sensors association: TE Solid Core; TR/iTR split Core; TF Flexible
- Frequency accuracy: Class 0.02
- Frequency range: 45-65 Hz
- Frequency rating: 50/60 Hz
- Load type: To be configured in the module:
1P+N - 1CT
2P - 1CT
2P+N - 2CT
3P - 1CT
3P - 2CT
3P - 3CT
3P+N - 1CT
3P+N - 3CT - Measurement level: Power Quality Analysis
- Network type: To be configured in the module:
1P+N
2P
2P+N
3P
3P+N - Number of current inputs: 3
- Number of Digital inputs/outputs: 3 Digital inputs / 2 Digital outputs
- Number of measurement points: 1
- Pulse counter: Yes, 3 Digital inputs
- Voltage connection: Removable spring-cage terminal, 2 x 6 positions, 0.5 … 2.5 mm² solid cable or 0.25 … 1.5 mm² stranded cable with ferrule
- Voltage measurement accuracy: Class 0.2
- Voltage measurement range Ph/N: 50-300 VAC
- Voltage measurement range Ph/Ph: 87-520VAC
- Voltage measurement type: AC
- Voltage Sampling rate: 9.6 kHz
- Voltage transformer: Optional
- Voltage transformer primary: To be configured
- Voltage transformer secondary: To be configured
- Cut-out type: 92mm x 92mm
- Display type: Display with 10 capacitive keys
- Integrated keyboard: Yes
- Number of function buttons: 10
- Number of pixels, horizontal: 350
- Number of pixels, vertical: 160
- RS485 connection: Removable screw terminal, 3 positions, 0.14 to 1.5 mm² stranded or solid cable
- Communication characteristics
- Electrical characteristics
- Environnement
- Environmental characteristics
- General characteristics
- Measurement characteristics
- Mechanical characteristics