48290000
- General information
- Product Range: DIRIS B-30
- Long Description: DIRIS B-30 RS485 Modbus 230VAC
- Short Description: DIRIS B-30 RS485 Modbus 230VAC
- Certificates and declaration
- Conformity to standard #3: CEC Compliant
- Conformity to standard #4: E257746 Vol.X5 Sec.A7
- Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
- Container Information
- EAN13: 3596032773083
- Package Level 1 Gross Weight: 0.22
- Package Level 1 Length: 0.08
- Package Level 1 Units: B
- Package Level 1 Width: 0.06
- Main
- Reference: 48290000
- General product characteristics
- Device type: Multifunction Power metering and monitoring device (PMD)
- Ordering
- Country of origin: FR
- Standards and regulations
- ANSI C12.20: Class 0.2
- Immunity to conducted disturbances: 400A/m LEVEL IV
- Immunity to electrical fast transients/bursts: LEVEL IV
- Immunity to electrostatic discharges on contact: LEVEL III
- Immunity to electrostatic fields in the air: LEVEL III
- Immunity to power frequency magnetic fields: CLASS B
- Immunity to radiated electromagnetic fields: LEVEL IV
- Surge immunity in common mode: LEVEL III
- IEC 61557-12: Class 0.5 for the global measurement chain
- Safety standards: IEC/EN 61010-1
UL 61010-1
CAN/CSA C22.2 No. 61010-1 - UL file number: E257746
- UL product category: PICQ/PICQ7
- Accuracy
- Electromagnetic compatibility
- PMD
- Safety
- Safety standard
- Technical characteristics
- Communication Ports: RS485 output
- Communication Protocols: Modbus RTU
- Communication speed: 1200-115200 bauds
- Physical layer: RS485 2-3 half duplex wires - SELV
- USB port interface: 1 Type B micro USB; Upgrade and configuration of the module
- Device power consumption (VA): ≤ 2
- Input voltage: 110-230 VAC +/- 15%
- Power supply connection: Removable spring-cage terminal, 2 x 2 positions, 0.5 … 2.5 mm² solid cable or 0.25 … 1.5 mm² stranded cable with ferrule
- Power supply frequency: 50/60 Hz
- Power supply type: AC
- Relative humidity: 55 °C / 131 °F / 97% RH (IEC 60068-2-30)
- Storage temperature: -25 … +85 °C (IEC 60068-2-1/IEC 60068-2-2)
- Impact resistance: Front panel: 5J - casing: 1J (IEC 61010-1 Ed 3.0)
- Maximum operating altitude: 6560 feet / 2000 m
- Operating temperature: -10 … +70 °C / +14 °F … +158 °F (IEC 60068-2-1/IEC 60068-2-2)
- PEP ecopassport - ISO 14025: SOCO-2014-01-v1-fr, SOCO-2014-01-v1-en
- Vibration: 0.35 mm, 25 Hz, 20 min/axe (IEC 61557-12)
- Display compatibility: DIRIS D-30
DIRIS Digiware D-50
DIRIS Digiware D-70 - Webserver compatibility: WEBVIEW-M
WEBVIEW-L - Active Energy accuracy: Class 0.2 ANSI C12.20
Class 0.5 for the global measurement chain according to IEC 61557-12 from 2% up to 120% of the rated current (with TE/TF sensors) - Active Power accuracy: Class 0.2 ANSI C12.20
Class 0.5 for the global measurement chain according to IEC 61557-12 from 2% up to 120% of the rated current (with TE/TF sensors) - Alarms: 8 alarms with configurable thresholds (low/high)
- Current measurement type: AC
- Digital input function: To be configured in device:
Logical status
Position of protection device or drawer (open/closed)
Trip status
Pulse metering
Synchronisation pulse - Digital input type: Optocoupler internal polarisation (12 VDC ± 10 %) or external polarisation (10-30VDC ± 10%)
- External sensors association: TE Solid Core; TR/iTR split Core; TF Flexible
- Frequency accuracy: Class 0.02
- Frequency range: 45-65 Hz
- Frequency rating: 50/60 Hz
- General measurements: Metering:
+/- kWh, +/- kvarh, kVAh
Multi-tariff (8 max)
Load curves
Multi-measurement:
V1, V2, V3, U12, U23, U31, f
I1, I2, I3, In, ∑P, ∑Q, ∑S, ∑PF
P, Q, S, PF per phase
Predictive Power
Voltage Ph/N unbalance
Voltage Ph/Ph unbalance
Current unbalance (Inba, Idir, Iinv, Ihom, Inb)
Phi, cos Phi, tan Phi - Load type: To be configured in the module:
1P+N - 1CT
2P - 1CT
2P+N - 2CT
3P - 1CT
3P - 2CT
3P - 3CT
3P+N - 1CT
3P+N - 3CT - Measurement level: Power Quality Analysis
- Measurement updating period: Configurable from 200ms to 60s
- Network type: To be configured in the module:
1P+N
2P
2P+N
3P
3P+N - Number of current inputs: 4
- Number of Digital inputs/outputs: 2 Digital inputs
- Power Quality measurements: THD V1, V2, V3, U12, U23, U31, I1, I2, I3
Individual harmonics U, V, I (up to 63rd)
Voltage sags, swells, interruptions, current inrush - Pulse counter: Yes, 2 Digital inputs
- Reactive Energy accuracy: Class 2 for the global measurement chain with TE, TR or TF current sensors
- Voltage connection: Removable spring-cage terminal, 2 x 6 positions, 0.5 … 2.5 mm² solid cable or 0.25 … 1.5 mm² stranded cable with ferrule
- Voltage measurement accuracy: Class 0.2
- Voltage measurement range Ph/N: 50-300 VAC
- Voltage measurement range Ph/Ph: 87-520 VAC
- Voltage measurement type: AC
- Voltage Sampling rate: 9.6 kHz
- Voltage transformer: Optional
- Voltage transformer primary: To be configured
- Voltage transformer secondary: To be configured
- Dimensions: 3 modules wide (54mm)
- Communication characteristics
- Electrical characteristics
- Environnement
- Environmental characteristics
- General characteristics
- Measurement characteristics