Function

DIRIS Digiware Idc are DIN-rail mounted DC power monitoring modules. Associated with DIRIS Digiware Udc DC voltage measurement modules, they measure and monitor parameters such as power, energy and power quality of DC electrical circuits. With their design, they can be installed at the closest point to the circuit to measure.
The RJ12 current inputs allow a quick and error free connection to DC current sensors which are directly powered by the DIRIS Digiware Idc module (no external power supply needed).
Adding DIRIS Digiware Idc modules to the monitoring system is easily done by clicking an RJ45 cable. This allows great flexibility to users wishing to add more metering points in the future.

=-=-=-=-=-=- System =-=-=-=-=-=-
Fill rate E-Order Common 29
Fill rate E-Order Selection 60
Certificates and Declaration
Conformity to standard #1 UL 61010-1 Guide PICQ File E257746
Conformity to standard #2 CSA-C22.2 No. 61010-1
Conformity to standard #3 IEC 61557-12
Conformity to standard #4 E257746
Proposition 65 California WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
Standards
Conformity to standards
  • IEC
  • UL
Certificates and Declaration - Safety
Safety standards IEC/EN 61010-1 UL 61010-1 CAN/CSA C22.2 No. 61010-1
UL file number E257746
General Product Characteristics
Device type DC current measurement module for DIRIS Digiware DC system
Technical Characteristics
Application Metering
Model I-30DC
Number of current inputs 3
Type Current acquisition module
Technical Characteristics - Environmental
Maximum operating altitude 6560 feet / 2000 m
Operating temperature +14 °F … +158 °F / -10 … +70 °C
PEP ecopassport - ISO 14025 SOCO-00008-V01.01-EN
Relative humidity 131 °F / 55 °C / 97% relative humidity
Storage temperature -4 °F … +158 °F / -20 … +70 °C
Technical Characteristics - Measurement
Accuracy class Class 0.5 Curretn measurement
Current measurement type DC
General measurements KWH, Demand ProfilesDC Current, DC Power
ETIM - Electrical characteristics
Sampling frequency [Hz] 10000
Number of current measurement inputs 3
Voltage type (supply voltage) DC
Supply voltage DC [V] 0..24
Supporting protocol for IEC 61850 Ethernet No
Supporting protocol for OPC UA PubSub No
Supporting protocol for PROFIBUS No
Supporting protocol for Modbus Yes
Supporting protocol for PROFINET IO No
Supporting protocol for other bus systems No
With audit logging (audit log) No
With firmware signature Yes
With logging of security events (security event log) Yes
With Role Based Access Control (RBAC) No
Web server with HTTPS transfer protocol No
ETIM - Mechanical characteristics
Width [mm] 18
Height [mm] 90
Depth [mm] 65
Degree of protection (IP), front side IP20
ETIM - Technical features
Ampere meter Yes
Blind power meter Yes
With rotational speed meter No
Frequency meter No
Pulse counter No
Voltmeter No
Effective power measurement device Yes
Remote display No
Logistics
GTIN/EAN 3596033002885
Customs number 9030900000
Price unit PC
Weight of the packing unit 0.09
Length of the packing unit 0.12
Width of the packing unit 0.085
Depth of the packing unit 0.033
Product Details
Effective date 2018-02-01
Country of origin FR
Discount Policy 1EN60
Discount Policy Label MEASUREMENT SYSTEM PACKAGE
Classification
UNSPSC 83101808
ETIM Class EC002301
IGCC 6042