48290160 - DIRIS Digiware S-130 3XCurrent | Socomec

48290160


  Download
    General information
  • Product Range: DIRIS Digiware S
  • Long Description: DIRIS Digiware S-130 3xI; 3 Integrated current sensors; Class 0.5; Metering; 10-63 A
  • Short Description: DIRIS Digiware S-130 3XCurrent
    Certificates and declaration
  • Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
    Container Information
  • EAN13: 3596033020056
  • Package Level 1 Gross Weight: 0.09
  • Package Level 1 Length: 0.035
  • Package Level 1 Units:
  • Package Level 1 Width: 0.08
    Main
  • Reference: 48290160
    General product characteristics
  • Device type: Current measurement module with 3 integrated current sensors for DIRIS Digiware system
    Ordering
  • Country of origin: FR
    Standards and regulations
      Electromagnetic compatibility
    • Immunity to conducted disturbances: IEC 61000-4-6 LEVEL II CRITERION A
    • Immunity to electrical fast transients/bursts: IEC 61000-4-4 LEVEL IV CRITERION A
    • Immunity to electrostatic discharges on contact: IEC 61000-4-2 LEVEL III CRITERION A
    • Immunity to electrostatic fields in the air: IEC 61000-4-2 LEVEL IV CRITERION A
    • Immunity to power frequency magnetic fields: IEC 61000-4-8 400A/m CRITERION A
    • Immunity to radiated electromagnetic fields: 80MHz to 1GHz IEC 61000-4-3 LEVEL III CRITERION A
    • Radiated emissions: CISPR11 GROUP 1 - CLASS B
    • Surge immunity in common mode: IEC 61000-4-5 LEVEL II CRITERION B
      Safety
    • Safety standards: IEC/EN 61010-1
      UL 61010-1
      CAN/CSA C22.2 No. 61010-1
    • UL file number: E257746
      Safety standard
    • UL product category: PICQ/PICQ7/FTRZ/FTRZ7
    Technical characteristics
      Communication characteristics
    • USB port interface: 1 Type B micro USB; Upgrade and configuration of the module
      Environmental characteristics
    • PEP ecopassport - ISO 14025: SOCO-00006-v01.01-fr, SOCO-00006-v01.01-en
      General characteristics
    • Display compatibility: DIRIS Digiware D-40
      DIRIS Digiware D-50
      DIRIS Digiware D-70
    • Webserver compatibility: WEBVIEW-M
      WEBVIEW-L
      Measurement characteristics
    • Accuracy class: Class 0.5
    • Active Energy accuracy: Class 0.5
    • Active Power accuracy: Class 1
    • Current measurement type: AC
    • Current rating range: 10-63 A
    • General measurements: Metering:
      +/- kWh, +/- kvarh, kVAh

      Multi-measurement:
      I1, I2, I3, In, ∑P, ∑Q, ∑S, ∑PF
    • Integrated sensors: 3 Integrated current sensors
    • Load type: To be configured in the module:
      1P+N - 1CT
      2P - 1CT
      2P+N - 2CT
      3P - 1CT
      3P - 2CT
      3P - 3CT
      3P+N - 1CT
      3P+N - 3CT
    • Measurement level: Metering
    • Number of current inputs: 3
  • Aperture: 8x8 mm
  • Breaker center spacing: 3/4 in
  • Current sensor type: Solid core
  • Power consumption in VA: 0.35