48290500 - TE-18 5-20A Sensor | Socomec

48290500


  Download
    General information
  • Product Range: TE SOLID CORE Current Sensors
  • Long Description: TE-18 5-20A Sensor; Solid Core; RJ12 Secondary; Ø 8.6 mm; Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I
  • Short Description: TE-18 5-20A Sensor
    Certificates and declaration
  • Conformity to standard #4: E257746 Vol.X5 Sec.A7
  • Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
    Container Information
  • EAN13: 3596032776466
  • Package Level 1 Gross Weight: 0.03
  • Package Level 1 Length: 0.015
  • Package Level 1 Units: S
  • Package Level 1 Width: 0.009
    Main
  • Reference: 48290500
    General product characteristics
  • Device type: Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I
    Ordering
  • Country of origin: FR
    Standards and regulations
      Safety
    • Safety standards: IEC/EN 61010-1
      UL 61010-1
      CAN/CSA C22.2 No. 61010-1
    • UL file number: E257746
    Technical characteristics
      Electrical characteristics
    • Intermittent overload: 10x In for 1s
    • Max voltage (Phase/neutral): 300V
    • Rated withstand voltage: 3kV
      Environnement
    • Relative humidity: 95% RH without condensation
    • Storage temperature: -25 … +85 °C (IEC 60068-2-1/IEC 60068-2-2)
      Environmental characteristics
    • Maximum operating altitude: 6560 feet / 2000 m
    • Measurement category: CAT III
    • Operating temperature: -10 … +70 °C / +14 °F … +158 °F (IEC 60068-2-1/IEC 60068-2-2)
    • PEP ecopassport - ISO 14025: SOCO-2014-03-v1-fr, SOCO-2014-03-v1-en
      Measurement characteristics
    • Accuracy class: 0.5 for the global measurement chain (Associated with Digiware I, DIRIS B & DIRIS A-40)
    • Current measurement type: AC
    • Current rating range: 5-20A
    • Frequency rating: 50/60 Hz
    • Full measurement range: 0.1-24A
  • Aperture: Ø 8.6 mm
  • Breaker center spacing: 3/4 in
  • CT secondary connection type: RJ12
  • Current Sensor Secondary type: 100mV
  • Current sensor type: Solid Core