Function

TE solid-core sensors are used with DIRIS Digiware I, DIRIS A, or DIRIS B Power Monitoring Devices to measure currents from 5 to 2000 A with only 7 part numbers and with the same guaranteed accuracy. The quick RJ12 connection, and the integrated intelligence prevent, any connection or configuration errors.
Numerous accessories are available to mount the sensors in any type of electrical panel.

=-=-=-=-=-=- System =-=-=-=-=-=-
Fill rate E-Order Common 29
Fill rate E-Order Selection 100
Certificates and Declaration
Conformity to standard #1 UL 61010-1 Guide PICQ File E257746
Conformity to standard #2 CSA-C22.2 No. 61010-1
Conformity to standard #3 IEC 61557-12
Conformity to standard #4 ISO 14025
Proposition 65 California WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
Standards
Conformity to standards
  • IEC
  • UL
Certificates and Declaration - Safety
UL file number E257746
General Product Characteristics
Device type Current sensors for DIRIS A, DIRIS B & DIRIS Digiware I
Technical Characteristics
Model TE-18
Opening Diam. 0.33 in / 8.6 mm
Rated current [A] 25 ... 63 A
Secondary rated current RJ12
Technical Characteristics - Electrical
Intermittent overload 10x In for 1s
Max voltage (Phase/neutral) 300V
Rated withstand voltage 3kV
Technical Characteristics - Environmental
Maximum operating altitude 6560 feet / 2000 m
Measurement category CAT III
Operating temperature -10 … +70 °C / +14 °F … +158 °F (IEC 60068-2-1/IEC 60068-2-2)
PEP ecopassport - ISO 14025 SOCO-2014-03-v1-fr, SOCO-2014-03-v1-en
Relative humidity 95% RH without condensation
Storage temperature -25 … +85 °C / -13 °F … +185 °F (IEC 60068-2-1/IEC 60068-2-2)
Technical Characteristics - Measurement
Accuracy class 0.5 for the global measurement chain (Associated with Digiware I, DIRIS B & DIRIS A)
Current rating range 25 … 63 A
Current Sensor Secondary type 100mV
Current sensor type Solid Core
Degree of Pollution IP20 / IK06
Frequency rating 50/60 Hz
Full measurement range 0.5 … 75 A
ETIM - Electrical characteristics
Rated primary current [A] 63
Rated secondary current [A] 0.1
Rated secondary apparent power [VA] 0.1
Accuracy class 0.2S
Overcurrent limiting factor FS 10
Calibrated Yes
ETIM - Mechanical characteristics
With contact protection Yes
Height opening [mm] 8.6..8.6
Width opening [mm] 8.6..8.6
Opening diameter [mm] 8.6
Snap mounting Yes
With copper rail Yes
Secondary connection Plug-in connection
ETIM - Technical features
Model Through-feed current converter
Number of primary inputs 1
Logistics
GTIN/EAN 3596032776473
Customs number 8504312990
Price unit PC
Weight of the packing unit 0.03
Length of the packing unit 0.015
Width of the packing unit 0.11
Depth of the packing unit 0.13
Product Details
Effective date 2013-11-22
Country of origin FR
Discount Policy 1EN30
Discount Policy Label SENSORS
Classification
UNSPSC 83101808
ETIM Class EC002048
IGCC 6042