48290575 - TF-120 400-2000A Sensor | Socomec
range img

48290575

    General information
  • Product Range: TF Flexible Current Sensors
  • Long Description: TF-120 400-2000A Flexible current sensor; Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I; Rogowski; RJ12 Secondary; Ø 120 mm
  • Short Description: TF-120 400-2000A Sensor
    Certificates and declaration
  • Conformity to standard #4: -
  • Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
    Container Information
  • EAN13: 3596033018701
  • Package Level 1 Units:
    Main
  • Reference: 48290575
    General product characteristics
  • Device type: Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I
    Ordering
  • Country of origin: IT
    Standards and regulations
      Electromagnetic compatibility
    • Immunity to conducted disturbances: IEC 61000-4-6
      3V – LEVEL III [150Khz - 80Mhz]
      Less than 2% measurement error
    • Immunity to electrical fast transients/bursts: IEC 61000-4-4 LEVEL IV CRITERION A
    • Immunity to electrostatic discharges on contact: IEC 61000-4-2
      6kV contact – LEVEL III
      CRITERION A
    • Immunity to electrostatic fields in the air: IEC 61000-4-2
      8kV air – LEVEL III
      CRITERION A
    • Immunity to power frequency magnetic fields: IEC 61000-4-8
      100A/m – LEVEL V
      Applicable to 50Hz and 60Hz distribution networks
    • Immunity to radiated electromagnetic fields: IEC 61000-4-3
      80MHz to 1GHz: 10V/m – LEVEL III
      1.4GHz – 2GHz: 3V/m - LEVEL II
      2.0GHz – 2.7GHz: 1V/m – LEVEL I
      CRITERION A
    • Radiated emissions: EN 55022
    • Surge immunity in common mode: IEC 61000-4-5
      4kV Common mode, 2kV differential mode – LEVEL IV
    Technical characteristics
      Measurement characteristics
    • Accuracy class: 0.5 for the global measurement chain (Associated with Digiware I, DIRIS B & DIRIS A-40)
    • Current measurement type: AC
    • Current rating range: 400-2000A
    • Full measurement range: 8-2400A
  • Aperture: Ø 120 mm
  • CT secondary connection type: RJ12
  • Current Sensor Secondary type: 100mV
  • Current sensor type: Rogowski