97233040
- General information
- Product Range: ATYS
- Long Description: NON-AUTOMATIC TRANSFER SWITCH, ATYS r, UL 1008 Optional Stand-by, 400 A 3P Controller not included
- Short Description: ATYS UL400 A 3P
- Certificates and declaration
- Conformity to standard #1: UL1008
- Conformity to standard #4: E317092 Vol.1 Sec.10
- Proposition 65 California: WARNING This product can expose you to chemicals including styrene and bisphenol A (BPA), which is known to the State of California to cause cancer and birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
- Container Information
- EAN13: 3596032929572
- Package Level 1 Gross Weight: 9.0
- Package Level 1 Length: 0.53
- Package Level 1 Width: 0.402
- Main
- Reference: 97233040
- Ordering
- Country of origin: FR
- Technical characteristics
- Max. connection section / AWG: 600MCM / 2 X 250MCM
- Min. connection section / AWG: #4/2 X 1/0
- Endurance (number of operating cycles): 4050
- Short circuit rating at 600 VAC (kA): 100
- Type of fuse: J
- Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit capacity (ms): 50
- Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit rating (kA): 14
- Number of Poles: 3
- Operation voltage 2 P - 3/4 P: 240/600
- Rated operational current / 240 VAC resistive load (A): 400
- Rated operational current / 240 VAC “Total System” (A): 400
- Rated operational current / 480 VAC resistive load (A): 400
- Rated operational current / 480 VAC “Total System” (A): 400
- Rated operational current / 600 VAC resistive load (A): 400
- Rated operational current / 600 VAC “Total System” (A): 200
- Switching time / Duration of electrical blackout (s): 0.6
- Switching time / I to 0 or 0 to II (s): 0.85
- Switching time / I to II or II to I (s): 1.3
- UL General use rating (A): 400
- Connection terminals
- Mechanical characteristics
- Short-circuit capacity