    General information
  • Product Range: MODULYS GP UL CABINET
  • Long Description: MODULYS GP UL CABINET - Modular UPS from 25 to 100 + 25 kW, Seamless and risk-free scalability & upgrading for unpredictable evolutions
  • Short Description: MODULYS GP UL CABINET
    Container Information
  • EAN13: 8027122672122
  • Package Level 1 Units:
    Electrical characteristics
      Output (AC)
    • Power factor: > 0.99
    Environnement
  • Noise level (ISO 7779): ≤ 58 dBA
  • Storage temperature range: 23 to 122 °F / -5 to +50 °C
    Main
  • Reference: M4-S-100-HCA0
    Input
  • Input Rated frequency: 60 Hz ±10 %
  • Input Rated voltage: 480 V
  • Mains connection: bar
  • Voltage tolerance: 3ph 480 V (+15 /-15 %) up to -40 % @ 50 % of nominal load
    Ordering
  • Country of origin: IT
    Output
  • Connections: bar
  • Crest factor: ≥ 2.7
  • Output Rated frequency: 60 Hz
  • Output Rated voltage: 480 V
  • Protection: Overload, overcharge, deep discharge and short circuit
  • Wave form: Pure sine wave
    Standards
  • EMC: FCC part15 Class A
  • Safety: UL1778, CSA C22.2 N. 107.3-05, MET File E114654
    Technical characteristics
      Environnement
    • Operating ambient temperature: from 32 to 104 °F / 0 to +40 °C (from 59 to 77 °F / 15 to 25 °C for best battery life)
    UPS Cabinet
  • Dimensions D (in): 35.04
  • Dimensions D (mm): 890
  • Dimensions H (in): 77.76
  • Dimensions H (mm): 1975
  • Dimensions W (in): 23.62
  • Dimensions W (mm): 600
  • Weight kg: 473
  • Weight lbs: 1.0429999999999999