97233020 - ATYS UL200 A 3P | Socomec

97233020


  Download
    General information
  • Product Range: ATYS
  • Long Description: NON-AUTOMATIC TRANSFER SWITCH, ATYS r, UL 1008 Optional Stand-by, 200 A 3P Controller not included
  • Short Description: ATYS UL200 A 3P
    Certificates and declaration
  • Conformity to standard #1: UL1008
  • Conformity to standard #4: E317092 Vol.1 Sec.9
  • Proposition 65 California: WARNING This product can expose you to chemicals including styrene and bisphenol A (BPA), which is known to the State of California to cause cancer and birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
    Container Information
  • EAN13: 3596032929558
  • Package Level 1 Gross Weight: 7.77
  • Package Level 1 Length: 0.465
  • Package Level 1 Width: 0.325
    Main
  • Reference: 97233020
    Ordering
  • Country of origin: FR
    Technical characteristics
      Connection terminals
    • Max. connection section / AWG: 300MCM
    • Min. connection section / AWG: #6
      Mechanical characteristics
    • Endurance (number of operating cycles): 6050
      Short-circuit capacity
    • Short circuit rating at 600 VAC (kA): 100
    • Type of fuse: J
  • Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit capacity (ms): 25
  • Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit rating (kA): 10
  • Short circuit rating at with Square D JJ breaker 250 A - 2 P 240 VAC - 3/4 P 480 VAC (kA): 65
  • Number of Poles: 3
  • Operation voltage 2 P - 3/4 P: 240/600
  • Rated operational current / 240 VAC resistive load (A): 200
  • Rated operational current / 240 VAC “Total System” (A): 200
  • Rated operational current / 480 VAC resistive load (A): 200
  • Rated operational current / 480 VAC “Total System” (A): 100
  • Rated operational current / 600 VAC resistive load (A): 200
  • Rated operational current / 600 VAC “Total System” (A): 100
  • Switching time / Duration of electrical blackout (s): 0.6
  • Switching time / I to 0 or 0 to II (s): 0.85
  • Switching time / I to II or II to I (s): 1.3
  • UL General use rating (A): 200