Long Description: TF-200 600-4000A Flexible current sensor; Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I; Rogowski; RJ12 Secondary; Ø 200 mm
Short Description: TF-200 600-4000A Sensor
Certificates and declaration
Conformity to standard #4: -
Proposition 65 California: WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
Container Information
EAN13: 3596033018718
Package Level 1 Units:
Main
Reference: 48290576
General product characteristics
Device type: Current sensors for DIRIS A-40, DIRIS B & DIRIS Digiware I
Ordering
Country of origin: IT
Standards and regulations
Electromagnetic compatibility
Immunity to conducted disturbances: IEC 61000-4-6 3V – LEVEL III [150Khz - 80Mhz] Less than 2% measurement error
Immunity to electrical fast transients/bursts: IEC 61000-4-4 LEVEL IV CRITERION A
Immunity to electrostatic discharges on contact: IEC 61000-4-2 6kV contact – LEVEL III CRITERION A
Immunity to electrostatic fields in the air: IEC 61000-4-2 8kV air – LEVEL III CRITERION A
Immunity to power frequency magnetic fields: IEC 61000-4-8 100A/m – LEVEL V Applicable to 50Hz and 60Hz distribution networks
Immunity to radiated electromagnetic fields: IEC 61000-4-3 80MHz to 1GHz: 10V/m – LEVEL III 1.4GHz – 2GHz: 3V/m - LEVEL II 2.0GHz – 2.7GHz: 1V/m – LEVEL I CRITERION A
Radiated emissions: EN 55022
Surge immunity in common mode: IEC 61000-4-5 4kV Common mode, 2kV differential mode – LEVEL IV
Technical characteristics
Measurement characteristics
Accuracy class: 0.5 for the global measurement chain (Associated with Digiware I, DIRIS B & DIRIS A-40)
Current measurement type: AC
Current rating range: 600-4000A
Full measurement range: 12-4800A
Aperture: Ø 200 mm
CT secondary connection type: RJ12
Current Sensor Secondary type: 100mV
Current sensor type: Rogowski
Traceparts Registration
In order to download 3D models, you must register with Traceparts.