Function

ATyS non-automatic transfer switches are designed for use in total system optional standby applications for the safe transfer between a normal and an alternate power source.
The changeover is done in open transition and with minimum supply interruption during transfer ensuring full compliance with UL 1008. The ATyS is a full on-load disconnector where the main components are based on proven technology, also meeting requirements in UL 98 standard.

=-=-=-=-=-=- System =-=-=-=-=-=-
Fill rate E-Order Common 100
Fill rate E-Order Selection 75
Certificates and Declaration
Conformity to standard #1 UL1008
Conformity to standard #2 IEC 60947-6-1
Proposition 65 California WARNING This product can expose you to chemicals including styrene and bisphenol A, which is known to the State of California to cause cancer and birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
Standards
Conformity to standards UL
Certificates and Declaration - Safety
UL file number E317092
Technical Characteristics
Control operator RTSE
Number of poles 2
Rated current [A] 260
Technical Characteristics - Connection terminals
Max. connection section / AWG 600MCM / 2 X 250MCM
Min. connection section / AWG #4/2 X 1/0
Technical Characteristics - Environmental
Operating temperature -4 ... +122°F / -20 ... +50°C
Storage temperature -40 ... +158°F / -40 ... +70°C
Technical Characteristics - Mechanical
Endurance (number of operating cycles) 6050
Technical Characteristics - Power supply
Power supply / Supply voltage VAC 50/60 Hz 208-277 VAC ± 20%
Technical Characteristics - Short-circuit capacity
Auxiliary contacts / Electrical characteristics AC300
Operation voltage 2 P - 3/4 P 240/600
Rated operational current / 240 VAC resistive load 260
Rated operational current / 240 VAC “Total System” 260
Rated operational current / 480 VAC resistive load 260
Rated operational current / 480 VAC “Total System” 260
Rated operational current / 600 VAC resistive load 260
Rated operational current / 600 VAC “Total System” 200
Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit capacity 50
Short circuit rating at 600 VAC with “Any Breaker” (kA) / Short circuit rating 14
Short circuit rating at 600 VAC [kA] 65
Type of fuse J
Technical Characteristics - Switching time
Switching time / Duration of electrical blackout 0.6
Switching time / I to 0 or 0 to II 0.85
Switching time / I to II or II to I 1.3
ETIM - Electrical characteristics
Max. rated operation voltage Ue AC [V] 600
Rated operating voltage [V] 240..600
Rated permanent current Iu [A] 260
Rated short-time withstand current lcw [kA] 14
Conditioned rated short-circuit current Iq [kA] 65
Number of poles 2
ETIM - Mechanical characteristics
Suitable for floor mounting No
Suitable for front mounting 4-hole No
Suitable for front mounting centre No
Suitable for distribution board installation No
Suitable for intermediate mounting Yes
Colour control element Other
Degree of protection (IP), front side IP20
ETIM - Technical features
Version as main switch Yes
Version as maintenance-/service switch Yes
Version as safety switch Yes
Version as emergency stop installation No
Version as reversing switch Yes
Number of switches 2
Number of auxiliary contacts as normally open contact 3
Motor drive optional No
Motor drive integrated Yes
Voltage release optional No
Device construction Built-in device fixed built-in technique
Type of control element Other
Interlockable Yes
Type of electrical connection of main circuit Bolt connection
Logistics
GTIN/EAN 3596032772352
Customs number 8536508090
Price unit PC
Weight of the packing unit 8.99
Length of the packing unit 0.465
Width of the packing unit 0.338
Depth of the packing unit 0.325
Product Details
Effective date 2013-11-06
Country of origin FR
Discount Policy 1CB73
Discount Policy Label ATYS UL
Length of the product unit 0.26
Width of the product unit 0.377
Depth of the product unit 0.3205
Weight 8.99
Classification
UNSPSC 39122205
ETIM Class EC000216
IGCC 5177